S7841 - Four Channel Event Logger
Event Logger S7841
It is possible to download recorded values to the PC by a communication adapter.
Applications:
- record of door opening / closing
- monitoring of functions of a machine
- record of technological processes
- record of running hours
Event logger advantages:
- variability of PC connectivity - RS232, USB, Ethernet, GSM modem
- permanent connection to the PC enabled, data is possible to download even during logging
- large data memory 32000 values
- large dual line display, switchable
- robust case
- easy installation, locking enabled
- low power consumption from battery, battery life up to 4 years
- indication of remaining battery life, easy replacement of the battery
- logging start/stop is enabled in several ways: at certain time and date programmed from computer, by delivered magnet or depending on logical state on channel 4 input
- each logical state is possible to describe from the PC. Description is used on the list of the recorded values
- each logger is possible to describe with text of maximum 32 characters
- each channel is possible to describe with text of maximum 16 characters
- password protection is enabled to prevent unauthorized manipulation with logger
TECHNICAL PARAMETERS | |
---|---|
Number of binary inputs: | 4 |
Input signals: | from potential-less contact or two-state voltage signal - selection by the switch |
Parameters of the potential-less contact input: - minimum pulse duration: - max.number of changes at input: - current through closed contact: - voltage at open contact: - maximum voltage at the input: |
500 ms (shorter pulses may not be recorded) maximum 20 changes on all inputs in 10s interval 5 uA < 3.6 V ±30 V |
Parameters of voltage input: - minimum pulse duration: - max.number of changes at input: - low voltage level: - high voltage level: - current to the input: |
inputs are mutually galvanically isolated 500 ms (shorter pulses may not be recorded) maximum 20 changes on all inputs in 10s interval 0 to 2.0 V 3.0 to 30 V maximum 1.5 mA at 30V |
Terminal of input signals: | removeable WAGO 734, maximum cross section of leads 1,5mm2 |
Data logging modes: | noncyclic – logging stops after filling the memory cyclic – after filling memory oldest data is overwritten by new |
Memory capacity: |
noncyclic record - 16254 input signal changes cyclic mode - 15792 input signal changes |
Real time clock: | integrated calendar including leap years |
Real time clock error: | < 200 ppm (i.e. 0.02%, 17.28 s in 24 h) |
LCD display refresh: | 5 s |
Communication with the PC: |
via RS232 by means of COM adapter via USB by means of USB adapter via Ethernet by means of LAN adapter |
Power: | Lithium battery 3.6V, size AA, typical life 4 years, indication of remaining life |
Operating temperature range: | -30 to +70°C |
Dimensions without terminals: | 93 x 64 x 29 mm |
Weight: | 130 g |
Protection: | IP20 |
Warranty: | 2 years |
Example of monitoring of door contacts
Data logger accessories
Battery is included in delivery. No other accessory is included. For basic use it is necessary to order at minimum a COM adapter or USB adapter or LAN adapter for communication with computer, optionally a start/stop magnet, if needed to control logging the other way than directly from computer or by external binary signal.
Anytime it is possible to download free basic Windows program for data logger. Program enables to control all logger functions and viewing and printing of record in numerical and simple graphic format. It is possible to export recorded values to dbf or txt formats for further analysis.
OPTIONAL ACCESSORIES | ||
---|---|---|
SWR004 | Windows optional software for data logger - color printing, vertical and horizontal zooming of graphs and other functions. | |
SW100 | CD with free PC program | |
LP002 | COM adapter for communication with personal computer via RS232 serial port | |
LP003 | USB adapter for communication with personal computer via USB port | |
LP005 |
LAN adapter - external converter for communication with the PC via Ethernet, including ac/dc adapter 230Vac/5Vdc. Exceeding of adjusted limits is alarmed by sending e-mail message or trap. More information in manual of Ethernet interface in pdf |
|
LP004 | start/stop magnet | |
MD036 | self adhesive Dual Lock for easy installation | |
F9000 | wall holder secured against unauthorized removal | |
A4203 | spare Lithium battery 3.6V size AA | |
LP006 | GSM adapter for communication via GSM modem WaveCom Fastrack | |
MP009 | GSM modem WaveCom Fastrack M1306B, without accessories | |
MP009/1 | antenna for GSM modem WaveCom Fastrack, right-angled | |
MP009/2 | data cable for GSM modem Fastrack adjustment | |
MP009/3 | ac/dc adapter 230V/12V for GSM modem Fastrack |