with Ethernet interface
- temperature
- barometric pressure
- relative humidity
- dew point temperature
- absolute humidity
- specific humidity
- mixing ratio
- specific enthalpy
Ethernet sensor is designed for measurement of temperature, barometric pressure, relative humidity, dew point temperature, absolute humidity, specific humidity, mixing ratio or specific enthalpy. Degrees Celsius and Fahrenheit are user selectable. Large dual line LCD for simultaneous display of temperature, pressure or relative humidity or other calculated humidity interpretation is an advantage. Display is possible to switch off. State-of-the-art capacitive polymer sensor ensures excellent calibration long term stability, inertia against water and condensation. Transmitter is designed for use in non-aggressive environment.
APPLICATIONS - measuring of temperature, humidity, pressure at:
- server rooms
- telecommunication devices
- warehouses
- glasshouses
- manufacturers
- museums, archives, galleries
- air-conditioned rooms
- weather stations
MODES OF COMMUNICATION | |
---|---|
Modbus TCP: | Modbus TCP protocol enables to read measured values, set alarm limits, adjust the probe. |
Telnet: | Port 9999 enables to set alarm limits (lower, upper limits, hysteresis for measured values and time delay), e-mail addresses, SNMP addresses, probe description, refresh of www pages (10s to 65535s), set storing interval to history (10s to 65535s), enable each communication channel. Capacity of the history memory is 100 sets of temperature, humidity, pressure + computed values. Password protection of this port is enabled. Automatic IP address assignment from DHCP server is also enabled. |
WWW pages: | User selectable design of www pages enabling to display curve of measurement history. User can design the look of www pages and temperature, humidity, pressure + computed values history. |
SNMP: | It is possible to read actual values and alarm limits. In case of alarm creation warning message (trap) is sent to addresses defined by the user (maximum three addresses). |
SOAP: | Transmitter enables to send actual measured data in the format of SOAP message to selected web server in preset interval 10-65535 s. In case message is not received by the server till next message is sent, warning trap 1/2 is sent. |
There are the following options of alarm indication:
ALARM INDICATION OPTIONS | |
---|---|
E-mail: | In case of alarm creation warning e-mail message is sent to addresses defined by the user (maximum three addresses). |
SNMP: | In case of exceeding of adjusted temperature, humidity, pressure + computed value limits alarm is activated and warning trap is sent to user specified IP addresses (maximum 3 addresses). |
WWW pages: | In case of exceeding of adjusted temperature, humidity, pressure + computed value limits active alarm is displayed on www page. |
syslog: | Transmitter enables to send text messages to selected syslog server after different events appear. E.g. after transmitter restart, alarm activation, communication error with SNTP, write to transmitter via mdb, sntp, after firmware change, after alarm termination, after communication error with SOAP server. |
TECHNICAL PARAMETERS | |
---|---|
Operating relative humidity range: | 0 to 100% |
Accuracy of relative humidity measurement: | ±2.5% relative humidity from 5 to 95% at 23°C |
Temperature measurement accuracy of T3511, T7511, T4511: | ±0.4°C |
Temperature measurement accuracy of T3510, T7510, T0510: | ±0.6°C |
Available temperature units: | degrees Celsius, Fahrenheit |
Accuracy and range of dew point temperature output of T3511, T7511: | ±1,5°C at ambient temperature T<25°C and RH>30% range -60 to +80 °C |
Accuracy and range of dew point temperature output of T3510, T7510: | ±1,8°C at ambient temperature T<25°C and RH>30% range -60 to +80 °C |
Accuracy and range of absolute humidity output: | ±3g/m3 at ambient temperature T < 40°C range 0 to 400 g/m3 |
Accuracy and range of specific humidity output of T3511, T7511: | ±2g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
Accuracy and range of specific humidity output of T3510, T7510: | ±2.1g/kg at ambient temperature T < 35°C range 0 to 550 g/kg |
Accuracy and range of mixing ratio output of T3511, T7511: | ±2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
Accuracy and range of mixing ratio output of T3510, T7510: | ±2.2g/kg at ambient temperature T < 35°C range 0 to 995 g/kg |
Accuracy and range of specific enthalpy output of T3511, T7511: | ±3kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
Accuracy and range of specific enthalpy output of T3510, T7510: | ±4kJ/kg at ambient temperature T < 25°C range: 0 to 995 kJ/kg |
Accuracy and range of barometric pressure output: | ± 1.3hPa at 23°C range: 600 to 1100hPa |
Supported pressure units: | hPa, kPa, mbar, mmHg, inHg, inH2O, PSI, oz/in^2 |
Temperature operating range of case with electronics: | -30 to +80°C |
Temperature operating range of LCD display: | readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C |
Range of RH sensor temperature compensation: | -30 to +105°C |
Filtering ability of sensor cover: | 0.025mm |
Protection: | IP30 electronics, IP40 sensors |
LAN connection: | RJ-45 connector |
Power: | 9-30Vdc, maximum consumption 1W |
Power connector: | co-axial, diameter 5.5 x 2.1 mm |
Dimensions of the case (W x H x D): |
88 x 73 x 37 mm |
Warranty: | two years |
Type | Measured value | Maximum range of temperature measurement | Note |
---|---|---|---|
T3510 |
temperature humidity |
-30 to +80°C |
Thermometer-hygrometer for ambient temperature, humidity measurement. Built-in sensors. |
T3511 |
temperature humidity |
-30 to +105°C* probe, cable + 80°C max, optionally with cable up to +105°C |
Thermometer-hygrometer. T+RH probe with 1m cable. Cable lengths 2m or 4m available optionally. Mechanical drawing |
T7510 |
temperature humidity barometric pressure |
-30 to +80°C
Pressure: 600 to 1100hPa accuracy: +/-1,3hPa at 23°C |
Thermometer-hygrometer-barometer for ambient temperature, humidity, pressure measurement. Built-in sensors. Reading and pressure output in these units: hPa, kPa, mbar, mmHg, inHg, inH2O, PSI, oz/in^2. Barometer enables to measure sea level pressure by setting of correction to altitude above sea level. |
T7511 |
temperature humidity barometric pressure |
-30 to +105°C* probe, cable + 80°C max,
optionally with cable up to +105°C
Pressure: 600 to 1100hPa accuracy: +/-1,3hPa at 23°C |
Thermometer-hygrometer-barometer. T+RH probe with 1m cable. Cable lengths 2m or 4m available optionally. Pressure sensor is located in the control unit with display. Reading and pressure output in these units: hPa, kPa, mbar, mmHg, inHg, inH2O, PSI, oz/in^2. Barometer enables to measure sea level pressure by setting of correction to altitude above sea level. Mechanical drawing |
T2514 |
barometric pressure |
600 to 1100hPa accuracy: +/-1,3hPa at 23°C |
Barometer. Reading and pressure output in these units: hPa, kPa, mbar, mmHg, inHg, inH2O, PSI, oz/in^2. Barometer enables to measure sea level pressure by setting of correction to altitude above sea level. |
T0510 |
temperature | -30 to +80°C |
Ambient temperature thermometer with built-in sensor |
T4511 |
temperature | -200 to +600°C |
Temperature transducer for RTD Pt1000/3850ppm probes |
* Relative humidity at temperature over +85°C is limited in accordance with the graph. Near plastic case with electronics and probe cable maximum temperature is +80°C.
Figure: Working range of Ethernet sensor
Included accessory:
Traceable calibration certificate from the manufacturer, instruction manual.
Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.
Free program TSensor for configuring of the transmitter is ready to download.
Free program SensorReader for logging values from one transmitter to a PC disk file is ready to download. Recorded values in CSV format are easy to process in e.g. Excel.
For acquiring values from several transmitters, third party software is necessary to use. Tested functionality is with programs
TIRS.NET,
ControlWeb,
EasyView. For record of values to graphs via web interface, project Cacti
www.cacti.net
is available.
OPTIONAL ACCESSORY | ||
---|---|---|
F5200B | black sensor cover with filter from stainless steel mesh, filtering ability 0,025mm | |
F0000 | sintered bronze sensor cover. Filtering ability 0.025mm. | |
PP4 | flat plastic circular flange for duct mounting | |
PP90 | right-angled stain-less steel flange for wall mounting | |
SP004 | plastic gland for direct mounting of the humidity probe to a 29 mm diameter hole | |
MD036 | self adhesive Dual Lock for easy installation | |
Solar radation shield | ||
A1515 | adapter 230V-50Hz/12Vdc | |
accessory for calibration and adjustment of humidity by the user |