Intelligent Ethernet thermometers for Pt1000

T0510 Ethernet sensor - temperature transducer

Ethernet thermometer T0510 is designed for ambient temperature measurement. Transducer T4511 is designed for conversion of temperature signal from external probes with Pt1000/3850 sensor (not included) to Ethernet interface. Degrees Celsius and Fahrenheit are user selectable. Ethernet sensor is built in a durable plastic case. Large dual line LCD is an advantage. Display is possible to switch off.

APPLICATIONS - measuring and control of temperature at:

MODES OF COMMUNICATION
Modbus TCP: Modbus TCP protocol enables to read measured values, set alarm limits, adjust the probe.
Telnet: Port 9999 enables to set alarm limits (lower, upper limits, hysteresis for temperature and time delay), e-mail addresses, SNMP addresses, probe description, refresh of www pages (10s to 65535s), set storing interval to history (10s to 65535s), enable each communication channel. Capacity of the history memory is 100 values. Password protection of this port is enabled. Automatic IP address assignment from DHCP server is also enabled.
WWW pages: User selectable design of www pages enabling to display curve of measurement history. User can design the look of www pages and temperature history.
SNMP: It is possible to read actual values and alarm limits. In case of alarm creation warning message (trap) is sent to addresses defined by the user (maximum three addresses).
SOAP: Transmitter enables to send actual measured data in the format of SOAP message to selected web server in preset interval 10-65535 s. In case message is not received by the server till next message is sent, warning trap 1/2 is sent.
Thermometer enables to monitor measured values. In case of exceeding of adjusted limits warning message can be sent to specified addresses.
There are the following options of alarm indication:
ALARM INDICATION OPTIONS
E-mail: In case of alarm creation warning e-mail message is sent to addresses defined by the user (maximum three addresses).
SNMP: In case of exceeding of adjusted temperature limits alarm is activated and warning trap is sent to user specified IP addresses (maximum 3 addresses).
WWW pages: In case of exceeding of adjusted temperature limits active alarm is displayed on www page.
syslog: Transmitter enables to send text messages to selected syslog server after different events appear. E.g. after transmitter restart, alarm activation, communication error with SNTP, write to transmitter via mdb, sntp, after firmware change, after alarm termination, after communication error with SOAP server.
Synchronizing of time and record to www table and temperature history is enabled by SNTP via Internet.
TECHNICAL PARAMETERS
Available temperature units: degrees Celsius, Fahrenheit
T0510 thermometer measuring range: -30 to +80°C
Accuracy of T0510 thermometer: ±0.6°C
Measuring range of T4511 transducer: -200 to +600°C
Accuracy of T4511 transducer input without probes: ±0.2°C
Temperature operating range of case with electronics: -30 to +80°C
Temperature operating range of LCD display: readable to operating temperature +70°C, it is recommended to switch OFF the LCD over +70°C
Protection of the case with electronics: IP20 electronics
LAN connection: RJ-45 connector
Power: 9-30Vdc, maximum consumption 1W
Power connector: co-axial, diameter 5 x 2.1 mm
Dimensions of the T0510 case: 88 x 126 x 37 mm (W x H x D)
Dimensions of the T4511 case: 88 x 98 x 37 mm (W x H x D)
Warranty: two years
TypeMaximum range of temperature measurementNote

T0510

Ethernet sensor - larger photo
-30 to +80°C Ambient temperature thermometer with built-in temperature sensor

Ethernet sensor - manual in pdfManual in pdf

Ethernet sensor - manual in pdfAppendixes for Manual

T4511

Ethernet sensor - larger photo
-200 to +600°C Temperature transducer from external probes with Pt1000/3850 sensor (not included - see Optional Accessory)

Ethernet sensor - manual in pdfManual in pdf

Ethernet sensor - manual in pdfAppendixes for Manual

Included accessory:

Traceable calibration certificate from the manufacturer, instruction manual. Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.

Free program TSensor for configuring of the transmitter is ready to download.
Free program SensorReader for logging values from one thermometer to a PC disk file is ready to download. Recorded values in CSV format are easy to process in e.g. Excel.
For acquiring values from several transmitters, third party software is necessary to use. Tested functionality is with programs TIRS.NET, ControlWeb, EasyView. For record of values to graphs via web interface, project Cacti www.cacti.net is available.

OPTIONAL ACCESSORY
Pt1000 probe
Pt1000 probe
probes temperature probes with Pt1000/3850ppm sensor without connector - probe marking is followed by symbol /0. Recommended is multi-purpose watertight probe Pt1000TG8/0 available with cable lengths 1, 2, 5, 10m
Larger photo of temperature transducer Dual Lock MD036 self adhesive Dual Lock for easy installation
Larger photo of adapter for thermometer A1515 adapter 230V-50Hz/12Vdc