Temperature probes and transducers
Pt1000, Pt100 / current 4-20mA

photo of probe P0120

Temperature probe P0120

P0120 - air temperature probe
with 4-20mA output, outdoor, indoor use

TECHNICAL PARAMETERS
Temperature measuring and operating range:
-30 to +80°C
Accuracy: ±0.4°C
Applied sensor: Pt1000/3850ppm
Break of sensor: >24mA
Short circuit of sensor: <3.5mA
Dimensions (W x H x D): approximately 89 x 151 x 37mm
Protection: IP65
Power: 9 to 30 V dc (typically 24V)
Warranty: two years

photo of transducer Px1x1

Temperature transducer Px1x1

Temperature transducers from Pt1000, Pt100 sensor to current 4-20mA

TECHNICAL PARAMETERS
Operating temperature:
-30 to +80°C
Break of sensor: >24mA
Short circuit of sensor: <3.5mA
Dimensions (W x H x D): approximately 89 x 123 x 37mm
Protection: IP65
Power: 9 to 30 V dc (typically 24V)
Warranty: two years

Available types of Pt1000 transducers, two-wire connection

Typ Temperature range
of 4-20mA output
Accuracy of the input
P4141 -100 to +30°C ±0.3°C
P4121 -30 to +80°C ±0.3°C
P4151 0 to +35°C ±0.2°C
P4131 0 to +150°C ±0.3°C
P4161 0 to +250°C ±0.4°C
P4171 0 to +400°C ±0.7°C

Transducers P41x1 are directly compatible with Comet temperature probes with the Pt1000 sensor with no connector - probe marking followed by /0 .

Manual in pdfManual for P0120 and P41x1 in pdf format

Available types of Pt100 transducers, two-wire, three-wire and two-wire with compensation loop connection

Typ Temperature range
of 4-20mA output
Accuracy of the input
P6181 -100 to +200°C ±0,3 °C up to +100°C,
±0,4°C over +100°C

Manual in pdfManual for P6181 in pdf format

Included is traceable calibration certificate from the manufacturer, instruction manual. Calibration certificate with declared metrological traceability of etalons is based on requirements of EN ISO/IEC 17025 standard.
Example of calibration certificate.

barometer wiring

Typical application wiring

Calculation of minimum power voltage Uss for proper operation:
Uss min> Uo min + Imax * Rz,
where: Uo min= 9 V
Imax... approximately 20 mA
Rz... sensing resistor (shunt)

sber dat Transmitters are directly compatible with sixteen channel Comet data acquisition system MS.